1W415-0791 / C / 04.18.12INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.NEVER LEAVE CHILDREN OR O
10W415-0791 / C / 04.18.123.1 VENTING LENGTHS AND COMPONENTSUse only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or
11W415-0791 / C / 04.18.123.2 TYPICAL VENT INSTALLATIONS30 1/2"TOP VENTREAR VENT16" MINIMUM40 FEET MAXIMUM 34" MINIMUM16" MINIMUM
12W415-0791 / C / 04.18.1220 FT MAX12” MINIMUM TO GRADE24” MINIMUM REGARDLESS OF HORIZONTAL VENT LENGTHMAX. HORIZONTAL RUN34" MAXIMUM 29" MI
13W415-0791 / C / 04.18.12Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when fi nal grading
14W415-0791 / C / 04.18.123.4 VENT TERMINAL CLEARANCESINSTALLATIONSCANADA U.S.A.A 12” 12” Clearance above grade, veranda porch, deck or balcony.B 12”
15W415-0791 / C / 04.18.123.5 VENTING APPLICATION FLOW CHART13.1TOP EXITHorizontal TerminationVertical TerminationVertical rise is equal to or greate
16W415-0791 / C / 04.18.123.6 DEFINITIONS3.7 ELBOW VENT LENGTH VALUES14.1For the following symbols used in the venting calculations and examples are:
17W415-0791 / C / 04.18.123.8 TOP EXIT HORIZONTAL TERMINATION(HT) > (VT) Simple venting configuration (only one 90° elbow)See graph to determine t
18W415-0791 / C / 04.18.123.9 TOP EXIT HORIZONTAL TERMINATION16.1ASimple venting confi guration (only one 90° elbow)(HT) < (VT)For vent confi gurati
19W415-0791 / C / 04.18.123.10 REAR EXIT HORIZONTAL TERMINATIONFor vent configurations requiring more than two 90° elbows, the following formulas app
2W415-0791 / C / 04.18.12NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.TABLE OF CONTENTS1.0 INSTALLATION OVERVIEW
20W415-0791 / C / 04.18.12Simple venting configuration (only two 90° elbows)See graph to determine the required vertical rise VT for the required hori
21W415-0791 / C / 04.18.123.11 TOP OR REAR EXIT VERTICAL TERMINATIONSimple venting configurations.See graph to determine the required vertical rise V
22W415-0791 / C / 04.18.12Simple venting configurations.See graph to determine the required vertical rise VT for the required horizontal run HT.REQUIR
23W415-0791 / C / 04.18.12Example:V1 = 1.5 FTV2 = 5 FTVT = V1 + V2 = 1.5 + 1 + 5 = 6.5 FTH1 = 1 FTH2 = 1 FTH3 = 10.75 FTHR = H1 + H2 + H3 = 1
24W415-0791 / C / 04.18.124.2 CHANGING A TOP VENT TO A REAR VENTIn order to convert the venting confi guration from a top exit to a rear exit, remove
25W415-0791 / C / 04.18.125.0 INSTALLATION!WARNINGFOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS EXACTLY.ALL INNER EX
26W415-0791 / C / 04.18.125.2 WALL AND CEILING PROTECTIONFor optimum performance, it is recommended that all horizontal runs have a minimum 1/4"
27W415-0791 / C / 04.18.125.2.2 VERTICAL INSTALLATIONThis application occurs when venting through a roof. Installation kits for various roof pitches a
28W415-0791 / C / 04.18.125.2.3 HORIZONTAL AIR TERMINAL INSTALLATION - MODEL CDVS600A. Stretch the inner fl ex pipe to the required length taking int
29W415-0791 / C / 04.18.125.2.4 VERTICAL AIR TERMINAL INSTALLATION - MODEL CDVS600A. Fasten the roof support to the roof using the screws provided. T
3W415-0791 / C / 04.18.121.0 INSTALLATION OVERVIEWCastings, see “FRONT CAST REMOVAL” section.Door, see “GLASS DOOR INSTALLATION AND REMOVAL” section.G
30W415-0791 / C / 04.18.125.3 APPLIANCE VENT CONNECTION - MODEL CDVS600A. Attach the adjustable pipe to the last section of rigid pipe. Secure with
31W415-0791 / C / 04.18.127.6This appliance is designed to be attached to a 3” co-linear aluminum fl ex vent system running the full length of a masonr
32W415-0791 / C / 04.18.12For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient location.
33W415-0791 / C / 04.18.125.8 NATURAL VENT SPECIFICS - MODEL CS6005.8.1 CHIMNEY INSTALLATION63.7A“A” VENT - SOLID FUEL WOOD BURNING CHIMNEY & VEN
34W415-0791 / C / 04.18.125.8.2 INSTALLING NATURAL VENTFollow the instructions of the "B" vent manufacturer for chimney installation.A. Rem
35W415-0791 / C / 04.18.125.8.5 ADDING VENT SECTIONSAdd chimney sections, according to the manufacturers installation instructions. The chimney must e
36W415-0791 / C / 04.18.125.8.6 INSTALLING FLASHING AND STORM COLLARSECURELY ATTACH VENT ADAPTER TO FLUE COLLAR4” “B” VENT7” OPTIONAL VENT PIPE3 FT MI
37W415-0791 / C / 04.18.126.0 FINISHINGA. Lift the top casting off.B. Lift the cast front out of its retainers (located at either side on the top).
38W415-0791 / C / 04.18.1214235Place log #1 onto the burner, centering it onto the burner tray and pushing it as close to the rear wall of the fi rebox
39W415-0791 / C / 04.18.1267Position the notch located in log #6 against the grate post.Place the bottom of log #7 against the right outermost grate p
4W415-0791 / C / 04.18.122.0 INTRODUCTION3.2B!WARNING• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.• ANY CHANGES OR
40W415-0791 / C / 04.18.126.7 SWITCH AND BRACKET INSTALLATION13CONNECT THE TWO WIRES TO THE SWITCH TERMINALS.2
41W415-0791 / C / 04.18.127.0 OPTIONAL BLOWER INSTALLATIONA. Ensure that the access cover plate has been installed. For location, see "SWITCH AN
42W415-0791 / C / 04.18.128.0 WIRING DIAGRAM69.5!WARNINGDO NOT WIRE 110 VOLTS TO THE VALVE OR WALL SWITCH.ON / OFF SWITCHACS/IPI SWITCH(OPTIONAL)DC BA
43W415-0791 / C / 04.18.129.0 OPERATIONMODEL CS600 ONLY: SPILL SWITCHThis is a thermally activated switch, attached to the back of the chimney adaptor
44W415-0791 / C / 04.18.129.2 OPERATING INSTRUCTIONS - FOR YOUR SAFETY READ BEFORE OPERATING9.3 LIGHTING INSTRUCTIONSLIGHTING INSTRUCTIONS / INSTRUCT
45W415-0791 / C / 04.18.1210.0 ADJUSTMENT10.1 PILOT BURNER ADJUSTMENTAdjust the pilot screw to provide properly sized fl ame. Turn in a clockwise dire
46W415-0791 / C / 04.18.12CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous oper
47W415-0791 / C / 04.18.1212.0 REPLACEMENTSContact your dealer or the factory for questions concerning prices and policies on replacement parts. Norma
48W415-0791 / C / 04.18.12CS600 COMPONENTSREF NO. PART NO. DESCRIPTION31 W010-0459 ADAPTOR C/W SPILL SWITCH 32 W660-0006 SPILL SWITCH33 W080-0405 SP
49W415-0791 / C / 04.18.12ACCESSORIESREF NO. CDVS600-1 CS600 DESCRIPTION18* W573-0007 W573-0007 HIGH TEMPERATURE SEALANT52* W690-0001 W690-0001 MILLI
5W415-0791 / C / 04.18.122.1 DIMENSIONS31 1/4"30 1/2"51/2"19 1/2"27"17 7/8"4" DIA.7" DIA.24"2.2 GENERAL I
50W415-0791 / C / 04.18.124548474664442436413743342527101234576313332442826569201159673584043435013125149
51W415-0791 / C / 04.18.1213.0 TROUBLESHOOTINGSYMPTOM PROBLEM TEST SOLUTIONPilot will not light.Makes noise with no spark at pilot burner.Wiring. - V
52W415-0791 / C / 04.18.12SYMPTOM PROBLEM TEST SOLUTIONCarbon is being deposited on glass, logs, rocks, media or combustion chamber surfaces.Air shutt
53W415-0791 / C / 04.18.1242.7_3BSYMPTOM PROBLEM TEST SOLUTIONWhite / grey fi lm forms.Sulphur from fuel is being deposited on glass, logs or combustio
54W415-0791 / C / 04.18.1214.0 WARRANTYCONTINENTAL® warrants its products against manufacturing defects to the original purchaser only. Registering yo
55W415-0791 / C / 04.18.1215.0 SERVICE HISTORY43.1
56W415-0791 / C / 04.18.12
6W415-0791 / C / 04.18.124.1A The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation
7W415-0791 / C / 04.18.12When the appliance is installed at elevations above 4,500ft, and in the absence of specifi c recommendations from the local au
8W415-0791 / C / 04.18.122.5 SHIPPING BRACKETSHIPPING BRACKET REMOVALA. Remove the four screws holding the shipping bracket to the bot-tom of the
9W415-0791 / C / 04.18.123.0 VENTING - MODEL CDVS6007.1ATHIS APPLIANCE USES A 4” EXHAUST / 7” AIR INTAKE VENT PIPE SYSTEM.Refer to the section applica